Mô tả

Bộ chuyển đổi BACnet/IP sang Modbus RTU ICP DAS GW-2492M CR

Features

  • Read/Write Modbus registers via BACnet objects
  • Configurable BACnet/IP Server
  • Configurable Modbus RTU Master
  • Supports BACnet AI, AO, AV, BI, BO, BV, MSI, MSO, MSV Object Types
  • Supports Modbus discrete inputs, coils, input registers and holding registers
  • Supports up to 600 DI, 600 DO, 600 AI and 600 AO to transfer to BACnet Objects
  • Simple data translation allows you to manipulate data as it passes between protocol

Introduction

GW-2492M is a network gateway allowing BACnet client devices to be accessed Modbus network as a Modbus RTU master. The BACnet/IP protocol is used to relay and exchange information between building devices. GW-2492M contains a large number of BACnet objects (AI, AO, AV, BI, BO, BV, MSI, MSO, MSV) gives you flexibility in mapping Modbus RTU registers to any combination of BACnet objects. Multiple BIBBs (DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM-B,…etc.) are supported. All the data transfer is configurable using a standard Web browser.

Applications

  • Building Automation
  • Heating, Ventilating, and Air-conditioning Control
  • Lighting Control
  • Access Control
  • Fire Detection Systems

Specifications

LED Indicators
Status Power (1), BACnet/IP Status (1), BACnet/IP Net(1),
Modbus RTU TxD/RxD/Link (3)
Ethernet LED Ethernet Status (RJ-45) (2)
COM Ports
Ports termninal block(D+, D-, TxD, RxD, GND)
Ethernet
Ports 1 x RJ-45, 10/100Base-TX
BACnet/IP
Protocol Modbus RTU Master (Supports up to 32 stations)
Objects AI, AO, AV, BI, BO, BV, MSI, MSO, MSV(Convert modbus 600 DI, 600 DO, 600 AI and 600 AO)
BIBBs DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM-B, DM-DDB-B, DM-DOB-B, DM-DCC-B, DM-RD-B
Power
Input Range +10 ~ +30 VDC
Consumption 5 W @ 24 VDC
Mechanical
Casing Metal
Dimensions (mm) 33 x 120 x 116
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing

Download

Datasheet

Documents

Ordering Information

GW-2492M     CR  BACnet/IP to Modbus RTU Gateway (RoHS)